6 | |||
7 | <pre> |
||
8 | TAB: GeneralSystem frequency 50Hz |
||
9 | |||
10 | Shore current 19.0 A |
||
11 | Overruled by remote checked |
||
12 | Dynamic current limiter unchecked |
||
13 | External current sensor connected (see manual) unchecked |
||
14 | State of charge when Bulk finished 95.0 % |
||
15 | Battery capacity 200 Ah |
||
16 | Charge efficiency 0.95 TAB: Grid |
||
17 | Country / grid code standard Germany: VDE-AR-N 4105:2018-11, internal NS protection |
||
18 | |||
19 | AC input 1 Above selected gridcode plus LOM B (compliant) |
||
20 | rise-in-voltage protection U> 253.0 V |
||
21 | start network service HF treshold 50.20 Hz |
||
22 | P(f>) droop 5.00 % |
||
23 | Use Aux1 as disable FeedIn signal checked |
||
24 | Maximum AC current for charge or feed in 100.0 % |
||
25 | Reactive power regulation Use a fixed Cos Phi |
||
26 | Filter time for reactive power 3.3 s |
||
27 | Cos phi at point 1 1.00 TAB: Inverter |
||
28 | PowerAssist unchecked |
||
29 | |||
30 | Inverter output voltage 230 V |
||
31 | Inverter DC shut-down voltage 44.00 V |
||
32 | Inverter DC restart voltage 48.00 V |
||
33 | Low DC alarm level 48.00 V |
||
34 | Do not restart after short-circuit (VDE 2510-2 safety) unchecked |
||
35 | enable AES uncheckedTAB: Charger |
||
36 | Enable charger checked |
||
37 | |||
38 | Weak AC input unchecked |
||
39 | Stop after excessive bulk unchecked |
||
40 | Lithium batteries checked |
||
41 | Disable VSense (for diagnostic purposes) unchecked |
||
42 | Configured for VE.Bus BMS unchecked |
||
43 | Charge curve Fixed |
||
44 | Absorption voltage 52.00 V |
||
45 | Float voltage 51.00 V |
||
46 | Charge current 70 A |
||
47 | Repeated absorption time 1.00 Hr |
||
48 | Repeated absorption interval 7.00 Days |
||
49 | Absorption time 1 HrTAB: Virtual switch |
||
50 | TAB: Usage |
||
51 | Virtual switch usage Do not use VS |
||
52 | TAB: Assistants |
||
53 | TAB: Assistant Configuration |
||
54 | ESS (Energy Storage System) (size:978) |
||
55 | |||
56 | *) System uses LiFePo4 with other type BMS |
||
57 | (This can be either a BMS connected via CAN bus or a BMS system in which the |
||
58 | batteries are protected from high/low cell voltages by external equipment.) |
||
59 | *) The battery capacity of the system is 200 Ah. |
||
60 | *) Sustain voltage 48.00 V. |
||
61 | *) Cut off voltage for a discharge current of: |
||
62 | 0.005 C= 46.00 V |
||
63 | 0.25 C= 46.00 V |
||
64 | 0.7 C= 46.00 V |
||
65 | 2 C= 46.00 V |
||
66 | *) Inverting is allowed again when voltage rises 1.20 V above cut-off(0). |
||
67 | *) Relevant VEConfigure settings: |
||
68 | - Battery capacity 200 Ah. |
||
69 | - PowerAssist unchecked |
||
70 | - Lithium batteries checked |
||